Water Treatment System Performance Report

Service Call Reason: Received a call from NMG complaining about the performance of the water treatment system.

Visit Date: October 15, 2025

Lab Sample Dates: October 18, 2025 & November 10, 2025

Location: Security Forces Hospital – Makkah

1. Pre-RO (Softened) Water Quality Comparison

Comparison of water samples against the required “Softened” water standard.

Parameter Unit of Measure Standard (Softened) Lab Result (RAW – 9 Nov) Lab Result (Pre-RO – 15 Oct) Lab Result (Soft – 9 Nov)
pH value-6.5–8.56.596.687.05
Hardnessmg/L<10 50(FAIL) 20
Conductivity (@25)µS<500396.1433396
Chloride (Cl)mg/L<60 95(FAIL) 115(FAIL) 100(FAIL)
Ironmg/L<0.30.230.060.05
Coppermg/L<0.1<0.001<0.001<0.001
Silica (SiO₂)mg/L≤2000.5
Phosphate (P₂O₂)mg/L<100.030.030.04

2. Post-RO (DI/RO) Water Quality Comparison

Comparison of DI/RO water samples against the required standard.

Parameter Unit of Measure Standard (DI/RO) Lab Result (W.CH.25.213 – 15 Oct) Lab Result (W.CH.25.235 – 10 Nov)
pH value-5–7.57.147.31
Hardnessmg/L 2 2 0
Conductivity (@25)µS5 51.6(FAIL) 6.87(FAIL)
Chloride (Cl)mg/L≤0.2 15(FAIL) 1.72(FAIL)
Ironmg/L≤0.100
Coppermg/L≤0.1<0.001<0.001
Silica (SiO₂)mg/L≤100.3
Phosphate (P₂O₂)mg/L≤0.50.050.02